NODUS
Equipment / Power generation

02 / POWER GENERATION

Power generation: gas engines and gas turbines

On-site generation for data centres: bridge, prime and backup power. Outputs are manufacturer ratings; site output is lower in heat and at altitude.

BrandModelOutput per unitFrequencySpeedNotesSource
CaterpillarG3520 Fast Response2.6 MW (50 Hz)50/60 Hz—10 s start to load↗
CaterpillarCG260-164.0–4.5 MW50/60 Hz—Continuous rating↗
INNIO JenbacherJ420up to 1.56 MW50/60 Hz——↗
INNIO JenbacherJ6203.5 MW50/60 Hz——↗
INNIO JenbacherJ624up to 4.5 MW50/60 Hz——↗
INNIO JenbacherJ920 FleXtra10.6 MW (50 Hz) / 9.5 MW (60 Hz)50/60 Hz——↗
Wärtsilä20V34SG9.8 MW (50 Hz) / 9.4 MW (60 Hz)50/60 Hz750 / 720 rpmMedium speed↗
Wärtsilä31SG11.4–12.8 MW50/60 Hz750 / 720 rpm—↗
Wärtsilä18V50SG18.4 MW (50 Hz) / 18.9 MW (60 Hz)50/60 Hz500 / 514 rpm—↗
MAN Energy Solutions20V35/44G12.8 MW (50 Hz) / 12.3 MW (60 Hz)50/60 Hz750 / 720 rpm—↗
MWMTCG 3020 V202.3 MW50/60 Hz1,500 rpm (50 Hz)—↗
Rolls-Royce mtuSeries 4000 gas1.0–2.5 MW50/60 Hz—8V to 20V↗

Which one do I need?

Bridge power in hot climates, under ~100 MW

Gas engine gensets: modular, easy N+1, hold output in heat.

Fast-start or mobile power

Aeroderivatives and trailer units: TM2500, SGT-A45 TR, FT8 MOBILEPAC.

Mid-size data centre campuses (20-60 MW)

Industrial turbines: Solar, SGT-400/600/800, Kawasaki L30A.

Heavy-duty frame: 7HA class.

What we need from you

Site frequency (50/60 Hz), MW needed and redundancy (N+1), design ambient temperature and altitude, fuel and gas pressure, grid-connected or island mode, target date.

We source new, surplus zero-hour and refurbished units. Every unit is verified by serial number with the OEM, and buyers arrange independent inspection.